Specifications

Main
Product range PowerLogic P3
Type of product or equipment Protection relay
Using the relay Universal
Product reference P3U30-5AAA1BCAA
Circuit breaker type 30TE
Food 480 V AC/DC
Measuring inputs : TC 1/5 A PHASE CURRENT 3
: TC 1/5 A residual current 1
: TP 101 V/110 V voltage 4
Number of digital inputs (DI) 16
number of analogue inputs 0
Number of digital outputs (DO) 1 guard dog
8
Number of analog outputs 0
Communication ports USB port 1 front
RJ45 2 rear
Communication protocols IEC 61850 ed. 1
IEC 61850 ed. 2
IEC 60870-5-101
DNP3 TCP
Modbus TCP
Ethernet IP
Communication protocol RSTP
PTP
Cybersecurity Communication port hardening
Password protection
Protective functions Phase overcurrent 50/51
Directional phase overcurrent 67
Earth fault overcurrent 50N/51N
Directional earth fault overcurrent 67N
Transient intermittent 67NI
Capacitor step unbalance 51C
Broken conductor 46 I2/I1
Selective overcurrent logic
Switch-on on fault (SOTF)
Circuit breaker failure 50BF
Directional active underpower 37P
Fault location 21FL
Recloser 79
Phase undercurrent 37
Long start, locked rotor 48/51LR
Motor restart inhibition 66
Capacitor overvoltage 59C
Negative sequence overcurrent 46 Overvoltage
59 Undervoltage 27 Positive sequence undervoltage 27P Residual overvoltage 59N Underfrequency 81/81N Frequency derivative 81R Synchronism check 25 Interlock 86 CT supervision 60 VT supervision 60 H2 detection 68H2 H5 detection H5 detection 68H5 Programmable thresholds 99 Programmable curve
 
Communication protocol No
Measuring functions Three-phase
current Zero sequence
current Positive component current
Negative component current Negative component
current Ratio current between negative sequence and positive
sequence Phase-to-earth
voltage Phase-to-phase
voltage Zero sequence
voltage Positive component
voltage Negative component
voltage Ratio voltage between negative sequence and positive sequence
Short-circuit fault reactance
Fault current location Earth
fault reactance
Frequency Active power RMS active power Reactive power RMS reactive power Apparent power RMS apparent power Active energy Reactive energy Cos φ Tan φ Power angle Power factor Synoptic phase voltage Synoptic phase current Current 2nd, 15th harmonics with TDH Voltage 2nd, 15th harmonics with TDH Voltage interruption Monitoring of the status of the switching devices
 
Control functions Circuit breaker control and monitoring
Programmable interlock
Local control on vector diagram
Local control with I/O keys
Local/remote control
2 function keys
Mobile application with EcoStruxureTM Power Device application
Web server
Programmable logic
Controllable devices 4 ordered + 8 displayed
Number of setting groups 4
Monitoring functions Trip circuit supervision 74
Circuit breaker supervision
Relay self-supervision
Records and recordings Event recording
Recording of oscilloscopes
Triggering context
Type of diagnostic cut-off organ TC/TP supervision ANSI code: 60
TC supervision
Tripping circuit supervision ANSI code: TCS
Connection mode Removable screw (logic input/output)
Removable pin (current transformer)
Removable pin (voltage transformer)
Complementary
Operating threshold 24…230 V DC
Synchronization protocol SNTP
Software Name EcoStruxure Power Device
ESetup Easergy Pro
Web Server Built-in HTTP server
Display type LCD 128 x 64 pixels with single-line synoptic
Number of keys 2 customizable
Voltage indication 4 LEDs
8 LEDs programmable
Standards IEC
height 169.5 mm
Width 170 mm
Depth 205 mm
Weight 2.5 kg maximum

 