Specifications

Main
Relay application Substation
Range of product Sepam series 40
Device short name S52
Control and monitoring type Latching/acknowledgement ANSI code: 86
Logic discrimination ANSI code: 68 (option)
Switching of groups of settings
Annunciation ANSI code: 30
Circuit breaker/contactor control ANSI code: 94/69
Logic equation editor 100 operators
Metering type Phase current I1, I2, I3 RMS, residual current I0
Demand current I1, I2, I3, peak demand current IM1, IM2, IM3
Voltage U21, U32, U13, V1, V2, V3, residual voltage V0
Frequency
Positive sequence voltage Vd/rotation direction-negative sequence voltage Vi
Active, reactive, apparent power P,Q,S-peak demand power PM, QM, power factor
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) (option)
Network and machine diagnosis type Unbalance ratio/negative sequence current Ii
Disturbance recording
Tripping context
Fault locator 21FL
Phase displacement
Switchgear diagnosis type Cumulative breaking current
Trip circuit supervision (option)
Number of operations, operating time charging time (option)
CT/VT supervision ANSI code: 60FL
Complementary
Type of measurement Voltage
Power (P,Q)
Peak demand power
Current
Power factor
Frequency
Energy
Protection type Recloser (4 cycles) ANSI code: 79 (option)
Neutral voltage displacement ANSI code: 59N (2)
Breaker failure ANSI code: 50BF (1)
Undervoltage protection ANSI code: 27/27S (2)
Overvoltage protection ANSI code: 59 (2)
Directional earth fault ANSI code: 67N/67NC (2)
Directional phase overcurrent ANSI code: 67 (2)
Cold load pick-up ANSI code: CPLU 50/51 (4)
Broken conductor ANSI code: 46BC (1)
Phase overcurrent ANSI code: 50/51 (4)
Earth fault/sensitive earth fault ANSI code: 50N/51N (4)
Earth fault/sensitive earth fault ANSI code: 50G/51G (4)
Negative sequence/unbalance ANSI code: 46 (2)
Negative sequence overvoltage ANSI code: 47 (1)
Overfrequency ANSI code: 81H (2)
Underfrequency ANSI code: 81L (4)
Directional active overpower ANSI code: 32P (1)
Cold load pick-up Io ANSI code: CPLU 50N/51N (4)
Communication port protocol Measurement readout ( option ) : Modbus
Remote indication and time tagging of events ( option ) : Modbus
Remote control orders ( option ) : Modbus
Remote protection setting ( option ) : Modbus
Transfer of disturbance recording data ( option ) : Modbus
Input output max capacity 10 inputs + 8 outputs
Communication compatibility Modbus TCPIP
DNP3
IEC 61850
IEC 60870-5-103
Modbus RTU
User machine interface type Remote
Without
Advanced

 