Specifications

Main
Using the relay Substation
Product range Sepam series 60
Device Name S62
type of control and monitoring Contactor/circuit breaker control ANSI code: 94/69 (option)
Acknowledgement/locking ANSI code: 86
Logic selectivity ANSI code: 68 (option)
Switching of groups of settings
Warning ANSI code: 30
Automatic transfer (AT) (option)
Editor of 200 logic operations
type of counting Positive sequence voltage Vd/direction of rotation
Frequency
Calculated active and reactive energy (+/- Wh, +/- VAR.h)
Active and reactive energy by pulse counting (+/- Wh, +/- VAR.h) (option)
Phase currents I1, I2, I3 RMS
Average current I1, I2, I3
Average peak current IM1, IM2, IM3
Measured residual current I”0
Voltage U21, U32, U13, V1, V2, V3
Residual voltage V0
Negative sequence voltage Vi
Active power P, P1, P2, P3
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Average peak power PM, QM
Power factor
Measured residual current I0, calculated I”0?
network and machine diagnostic type Unbalance rate/negative sequence current Ii
Oscilloscope recording
Used thermal capacity
Time remaining before overload tripping
Waiting time after overload tripping Tripping
context
Phase fault and earth fault trip counters
Total harmonic distortion (THD), current and voltage Ithd, Uthd
Difference in amplitude, frequency and phase of voltages with synchro-check option
Apparent positive sequence impedance Zd
Apparent impedances between phases Z21, Z32, Z13
Cable arcing fault detection
Phase displacement
Data log (DLG)
Type of diagnostic cut-off organ Cumulative breaking current
CT/TP supervision ANSI code: 60FL
Tripping circuit supervision ANSI code: 74 (option)
No. of operations, operating time, loading time, no. of unplugging operations (option)
Complementary
Type of measurement Energy
Peak Demand Power
Frequency
Power Factor
Harmonic Distortion (I THD & U THD)
Voltage
Current
Power (P,Q)
type of protection Recloser (4 cycles) ANSI code: 79 (option)
Neutral voltage displacement ANSI code: 59N (2)
Circuit breaker failure ANSI code: 50BF (1)
Directional earth fault ANSI code: 67N/67NC (2)
Directional phase overcurrent ANSI code: 67 (2)
Synchronism check ANSI code: 25 (option)
Phase overcurrent ANSI code: 50/51 (4)
Earth fault/sensitive earth fault ANSI code: 50N/51N (4)
Earth fault/sensitive earth fault ANSI code: 50G/51G (4)
Negative sequence/unbalance ANSI code: 46 (2)
Overfrequency ANSI code: 81H (2)
Underfrequency ANSI code: 81L (4)
Positive sequence undercurrent ANSI code: 27D (2)
Remaining undervoltage ANSI code: 27R (2)
Negative sequence overvoltage ANSI code: 47 (2)
Directional active overpower ANSI code: 32P (2)
Undervoltage (LL or LN) ANSI code: 27 (2)
Frequency drift ANSI code: 81R (2)
Overvoltage (LL or LN) ANSI code: 59 (2)
Thermal overload for cables ANSI code: 49RMS (1)
communication protocol Reading of measurements (option): Modbus
Remote indication and fixing of event time (option): Modbus
Remote commands (option): Modbus
Remote protection setting (option): Modbus
Transfer of disturbance recording data (option): Modbus
max. input/output capacity 28 inputs + 16 outputs
Communication Compatibility IEC 60870-5-103
TCPIP Modbus
Modbus RTU
Message goose IEC 61850
DNP3
IEC 61850
user machine interface type Dummy
Without
Remote
Evolved

 