Specifications

Main
Using the relay Engine
Product range Sepam series 60
Device Name M61
type of control and monitoring Contactor/circuit breaker control ANSI code: 94/69 (option)
Acknowledgement/locking ANSI code: 86
Logic selectivity ANSI code: 68 (option)
Switching of groups of settings
Warning ANSI code: 30
Editor of 200 logic operations
Automatic load shedding/restart
type of counting Positive sequence voltage Vd/direction of rotation
Frequency
Calculated active and reactive energy (+/- Wh, +/- VAR.h)
Active and reactive energy by pulse counting (+/- Wh, +/- VAR.h) (option)
Phase currents I1, I2, I3 RMS
Average current I1, I2, I3
Average peak current IM1, IM2, IM3
Voltage U21, U32, U13, V1, V2, V3
Residual voltage V0
Negative sequence voltage Vi
Active power P, P1, P2, P3
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Average peak power PM, QM
Power factor
Temperature (16 RTDs) (option)
Rotation speed (option)
Measured residual current I0, calculated I”0?
network and machine diagnostic type Unbalance rate/negative sequence current Ii
Oscilloscope recording
Used thermal capacity
Time remaining before overload tripping
Waiting time after overload tripping
Operating hours counter/running time
Starting current and duration
Start inhibit time, number of starts before inhibition
Tripping context
Phase fault and earth fault trip counters
Total harmonic distortion (THD), current and voltage Ithd, Uthd
Apparent positive sequence impedance Zd
Apparent impedances between phases Z21, Z32, Z13
Cable arcing fault detection
Phase displacement
Data log (DLG)
Motor start report (MSR)
Motor start trend (MST)
Type of diagnostic cut-off organ Cumulative breaking current
CT/TP supervision ANSI code: 60FL
Tripping circuit supervision ANSI code: 74 (option)
No. of operations, operating time, loading time, no. of unplugging operations (option)
Complementary
Type of measurement Power factor
Current
Rotational speed
Peak demand power
Harmonic distortion (I THD & U THD)
Frequency
Temperature
Voltage
Power (P,Q)
Energy
type of protection Thermostat / buchholz ANSI code: 26/63 (option)
Phase undercurrent ANSI code: 37 (1)
Departures per hour ANSI code: 66 (1)
Neutral voltage displacement ANSI code: 59N (2)
Circuit breaker failure ANSI code: 50BF (1)
Directional earth fault ANSI code: 67N/67NC (2)
Temperature monitoring (16 RTDs) ANSI code: 38/49T (option)
Thermal overload for machines ANSI code: 49RMS (2)
Long start, rotor jam ANSI code: 48/51LR (1)
Field loss (under-impedance) ANSI code: 40 (1)
Overspeed (2 setting points) ANSI code: 12 (option)
Underspeed (2 setting points) ANSI code: 14 (option)
Directional reactive overpower ANSI code: 32Q (1)
Maximum phase current ANSI code: 50/51 (4)
Earth fault/sensitive earth fault ANSI code: 50N/51N (4)
Earth fault/sensitive earth fault ANSI code: 50G/51G (4)
Negative sequence/unbalance ANSI code: 46 (2)
Overfrequency ANSI code: 81H (2) Underfrequency ANSI
code: 81L (4)
Positive sequence undercurrent ANSI code: 27D (2)
Remaining undervoltage ANSI code: 27R (2)
Negative sequence overvoltage ANSI code: 47 (2)
Directional active overpower ANSI code: 32P (2)
Undervoltage (LL or LN) ANSI code: 27 (2)
Overvoltage (LL or LN) ANSI code: 59 (2)
communication protocol Reading of measurements (option): Modbus
Remote indication and fixing of event time (option): Modbus
Remote commands (option): Modbus
Remote protection setting (option): Modbus
Transfer of disturbance recording data (option): Modbus
max. input/output capacity 28 inputs + 16 outputs
Communication Compatibility Modbus RTU
Message goose IEC 61850
IEC 60870-5-103
IEC 61850
TCPIP Modbus
DNP3
user machine interface type Dummy Free
Evolved Remote

 

Reviews

There are no reviews yet.

Be the first to review “SEPAM M61”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Be the first to review “SEPAM M61”

Your email address will not be published. Required fields are marked *