Specifications

Main
Relay application Generator
Range of product Sepam series 80
Sepam series 80 NPP
Device short name G82
Control and monitoring type Circuit breaker/contactor control ANSI code: 94/69 (option)
Latching/acknowledgement ANSI code: 86
Logic discrimination ANSI code: 68 (option)
Switching of groups of settings
Annunciation ANSI code: 30
Automatic transfer (AT) (option)
Logipam programming (ladder language) (option)
Logic equation editor 200 operators
Metering type Positive sequence voltage Vd/rotation direction
Frequency
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) (option)
Phase current I1, I2, I3 RMS
Demand current I1, I2, I3
Peak demand current IM1, IM2, IM3
Measured residual current I’0
Voltage U21, U32, U13, V1, V2, V3
Residual voltage V0
Negative sequence voltage Vi
Active power P, P1, P2, P3
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Peak demand power PM, QM
Power factor
Temperature (16 RTDs) (option)
Rotation speed (option)
Neutral point voltage Vnt
Measured residual current I0, calculated I’0∑
Network and machine

diagnosis type

Unbalance ratio/negative sequence current Ii
Disturbance recording
Thermal capacity used
Remaining operating time before overload tripping
Waiting time after overload tripping
Running hours counter/operating time
Tripping context
Phase fault and earth fault trip counters
Harmonic distortion (THD), current and voltage Ithd, Uthd
Difference in amplitude, frequency and phase of voltages with synchro-check option
Apparent positive sequence impedance Zd
Apparent phase-to-phase impedances Z21, Z32, Z13
Third harmonic voltage, neutral point residual
Phase displacement
Datalog (DLG)
Switchgear diagnosis type Cumulative breaking current
CT/VT supervision ANSI code: 60FL
Trip circuit supervision ANSI code: 74 (option)
Auxiliary power supply monitoring
Nb of operations, operating time, charging time, nb of racking out operations (option)
Complementary
Type of measurement Harmonic distorsion (I THD & U THD)
Voltage
Current
Power factor
Peak demand power
Power (P,Q)
Energy
Temperature
Frequency
Rotation speed
Protection type Thermostat / buchholz ANSI code: 26/63 (option)
Neutral voltage displacement ANSI code: 59N (2)
Breaker failure ANSI code: 50BF (1)
Directional earth fault ANSI code: 67N/67NC (2)
Directional phase overcurrent ANSI code: 67 (2)
Synchro-check ANSI code: 25 (option)
Overvoltage (L-L or L-N) ANSI code: 59 (4)
Temperature monitoring (16 RTDs) ANSI code: 38/49T (option)
Thermal overload for machines ANSI code: 49RMS (2)
Restricted earth fault ANSI code: 64REF (2)
Overfluxing (V/Hz) ANSI code: 24 (2)
Field loss (underimpedance) ANSI code: 40 (1)
Pole slip ANSI code: 78PS (1)
Overspeed (2 set points) ANSI code: 12 (option)
Underspeed (2 set points) ANSI code: 14 (option)
Directional reactive overpower ANSI code: 32Q (1)
Directional active underpower ANSI code: 32P (2)
Underimpedance ANSI code: 21B (1)
Inadvertent energisation ANSI code: 50/27 (1)
Third harmonic undervoltage/100 % stator earth fault ANSI code: 27TN/64G2 (2)
Third harmonic undervoltage/100 % stator earth fault ANSI code: 64G (2)
Negative sequence/unbalance ANSI code: 46 (2)
Overfrequency ANSI code: 81H (2)
Underfrequency ANSI code: 81L (4)
Positive sequence undercurrent ANSI code: 27D (2)
Remanent undervoltage ANSI code: 27R (2)
Undervoltage (L-L or L-N) ANSI code: 27 (4)
Negative sequence overvoltage ANSI code: 47 (2)
Phase overcurrent ANSI code: 50/51 (8)
Earth fault/sensitive earth fault ANSI code: 50N/51N (8)
Earth fault/sensitive earth fault ANSI code: 50G/51G (8)
Directional active overpower ANSI code: 32P (2)
Voltage-restrained overcurrent ANSI code: 50V/51V (2)
Communication port protocol Measurement readout ( option ) : Modbus
Remote indication and time tagging of events ( option ) : Modbus
Remote control orders ( option ) : Modbus
Remote protection setting ( option ) : Modbus
Transfer of disturbance recording data ( option ) : Modbus
Input output max capacity 42 inputs + 23 outputs
Communication compatibility DNP3
IEC 61850
Modbus TCPIP
IEC 60870-5-103
Modbus RTU
IEC 61850 goose message
User machine interface type Without
Remote
Mimic-based
Advanced

Reviews

There are no reviews yet.

Be the first to review “SEPAM G82”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Be the first to review “SEPAM G82”

Your email address will not be published. Required fields are marked *