Specifications

Main
Relay application Busbars
Range of product Sepam series 80 NPP
Sepam series 80
Device short name B80
Control and monitoring type Circuit breaker/contactor control ANSI code: 94/69 (option)
Latching/acknowledgement ANSI code: 86
Logic discrimination ANSI code: 68 (option)
Switching of groups of settings
Annunciation ANSI code: 30
Automatic transfer (AT) (option)
Logipam programming (ladder language) (option)
Logic equation editor 200 operators
Metering type Positive sequence voltage Vd/rotation direction
Frequency
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) (option)
Phase current I1, I2, I3 RMS
Demand current I1, I2, I3
Peak demand current IM1, IM2, IM3
Measured residual current I’0
Voltage U21, U32, U13, V1, V2, V3
Residual voltage V0
Negative sequence voltage Vi
Active power P, P1, P2, P3
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Peak demand power PM, QM
Power factor
Voltage U’21, V’1 and frequency
Measured residual current I0, calculated I’0∑
Network and machine diagnosis type Unbalance ratio/negative sequence current Ii
Disturbance recording
Tripping context
Phase fault and earth fault trip counters
Harmonic distortion (THD), current and voltage Ithd, Uthd
Difference in amplitude, frequency and phase of voltages with synchro-check option
Apparent positive sequence impedance Zd
Apparent phase-to-phase impedances Z21, Z32, Z13
Phase displacement
Datalog (DLG)
Switchgear diagnosis type Cumulative breaking current
CT/VT supervision ANSI code: 60FL
Trip circuit supervision ANSI code: 74 (option)
Auxiliary power supply monitoring
Nb of operations, operating time, charging time, nb of racking out operations (option)
Complementary
Type of measurement Current
Power (P,Q)
Peak demand power
Voltage
Energy
Frequency
Power factor
Protection type Neutral voltage displacement ANSI code: 59N (2)
Breaker failure ANSI code: 50BF (1)
Synchro-check ANSI code: 25 (option)
Overvoltage (L-L or L-N) ANSI code: 59 (4)
Negative sequence/unbalance ANSI code: 46 (2)
Overfrequency ANSI code: 81H (2)
Underfrequency ANSI code: 81L (4)
Remanent undervoltage ANSI code: 27R (2)
Negative sequence overvoltage ANSI code: 47 (2)
Phase overcurrent ANSI code: 50/51 (8)
Earth fault/sensitive earth fault ANSI code: 50N/51N (8)
Earth fault/sensitive earth fault ANSI code: 50G/51G (8)
Positive sequence undercurrent ANSI code: 27D (4)
Undervoltage (L-L or L-N) ANSI code: 27 (2)
Communication port protocol Measurement readout ( option ) : Modbus
Remote indication and time tagging of events ( option ) : Modbus
Remote control orders ( option ) : Modbus
Remote protection setting ( option ) : Modbus
Transfer of disturbance recording data ( option ) : Modbus
Input output max capacity 42 inputs + 23 outputs
Communication compatibility Modbus RTU
DNP3
Modbus TCPIP
IEC 61850
IEC 60870-5-103
IEC 61850 goose message
User machine interface type Without
Advanced
Mimic-based
Remote