Specifications

Main
Range of product PowerLogic P3
Product or component type Protection relay
Relay application Universal
product reference P3U20-5ABA1ACAA
Mounting case size 20TE
power supply 24…48 V DC
measuring inputs : 1/5 A CT phase current 3
: 1/5 A CT residual current 1
: 100 V/110 V VT voltage 1
number of Digital Inputs (DI) 10
number of analogue inputs 0
number of Digital Outputs (DO) 1 watchdog
5
number of analogue outputs 0
communication ports USB port 1 front
RJ45 2 rear
communication protocols IEC 61850 ed. 1
IEC 61850 ed. 2
IEC 60870-5-101
DNP3 TCP
Modbus TCP
EtherNet/IP
Redundancy communication port protocol RSTP
PRP
Cybersecurity Password protection
Port hardening
protection functions Phase overcurrent 50/51
Earth fault overcurrent 50N/51N
Directional earth fault 67N
Transient earth fault 67NI
Capacitor bank unbalance 51C
Broken conductor 46 I2/I1
Cold load pick-up
Switch ON to fault (SOTF)
Breaker failure 50BF
Recloser 79
Phase undercurrent 37
Excessive starting time, locked rotor 48/51LR
Motor restart inhibition 66
Capacitor overvoltage 59C
Negative sequence overcurrent 46
Earth fault overvoltage 59N
Rate of change of frequency 81R
Lockout relay 86
H2 detection 68H2
H5 detection 68H5
Programmable stages 99
Programmable curve
Arc flash protection No
measurement functions Current 3-phase
Current zero sequence
Current positive sequence
Current negative sequence
Current ratio of negative and positive
Voltage zero sequence
Earth fault reactance
Frequency
Current phasor diagram view
Current 2nd, 15th harmonics with THD
Condition monitoring CB wear
control functions Switchgear control and monitoring
Programmable switchgear interlocking
Local control on single-line diagram
Local control with I/O keys
Local/remote control
2 function keys
Mobile application with Easergy SmartApp
Web-server
Programmable logic
controllable switchgear devices 2 controlled + 4 displayed
number of setting groups 4
monitoring functions Trip circuit supervision 74
Circuit breaker monitoring
Relay self-monitoring
logs and records Event recording
Disturbance recording
Tripping context
Switchgear diagnosis type Trip circuit supervision ANSI code: TCS
CT supervision ANSI code: 60
Connections – terminals Screw removable (digital input/output)
Pin removable (current transformer)
Pin removable (voltage transformer)
Complementary
Operating threshold 24…230 V AC/DC
Time synchronisation protocol SNTP
Software name EcoStruxure Power Device
ESetup Easergy Pro
Web server Embedded HTTP server
Display type LCD 128 x 64 pixels with single line diagram
Number of key 2 customizable
Local signalling 4 LEDs
8 LEDs programmable
Standards IEC
Height 169.5 mm
Width 170 mm
Depth 205 mm
Net weight 2.5 kg maximum