Specifications
Product range | PowerLogic P5 |
---|---|
Type of product or equipment | Protection and relay control |
Using the relay | Maximum directional phase current |
Product reference | P5F30-BACD-GAAAA-AEAC |
Circuit breaker type | 30TE |
Mounting the device | Recessed |
Mounting bracket | Rack |
Installation mode | Detachable |
Food | 100…230 V AC 48…250 V DC |
Measuring inputs | : TC 1/5 A PHASE CURRENT 3 : TC 1/5 A residual current 1 : TC 1 A current 1 : voltage 4 : digital 15 |
Number of digital inputs (DI) | 15 |
number of analogue inputs | 0 |
Number of digital outputs (DO) | 1 watchdog 12 logic |
Number of analog outputs | 0 |
Communication ports | Front USB port 2 |
Cybersecurity | Password protection Communication port hardening Firmware signature Client IP address filter Secure communication with associated tools |
Protective functions | Phase overcurrent 50/51 Directional phase overcurrent 67 Earth overcurrent 50N/51N Directional earth overcurrent 67N Transient intermittent 67NI Neutral admission 21YN Broken conductor 46 I2/I1 Selective overcurrent logic Fault triggering (SOTF) Circuit breaker failure 50BF Directional active underpower 37P Phase undercurrent 37 Long start, rotor lock 48/51LR Motor restart inhibition 66 Negative sequence overcurrent 46 Overvoltage 59 Undervoltage 27 Positive sequence undervoltage 27P Residual overvoltage 59N Underfrequency 81/81N Overfrequency 81/81N Restricted earth fault 64REF Lockout 86 CT supervision 60 VT supervision 60 H2 detection 68H2 H5 detection 68H5 Wattmetric earth fault 32N Programmable thresholds 99 Programmable curve Programmable logic 46 I2/I1 Current unbalance 46 I2/I1 |
Communication protocol | No |
Measuring functions | Three-phase current Zero sequence current Positive component current Negative component current Ratio current between reverse and direct Zero sequence voltage Positive component voltage Negative component voltage Three- phase voltage Residual voltage Frequency Synoptic phase voltage Synoptic phase current Current 2nd, 15th harmonics with TDH |
Control functions | Circuit breaker control and monitoring Programmable interlock Local/remote control 2 function keys Programmable logic |
Controllable devices | 6 objects ordered + 2 objects monitored |
Number of setting groups | 4 |
Monitoring functions | Trip circuit supervision 74 Circuit breaker supervision Relay self-supervision |
Registers and records | Event recording Recording of oscilloscope disturbances Triggering context Relay maintenance |
Type of diagnostic cut-off organ | TC/TP supervision ANSI code: 60 TC supervision Tripping circuit supervision ANSI code: TCS |
Connection mode | Removable pin (logic input/output) Removable eye lugs (current transformer) Removable pin (voltage transformer) Eye lugs (voltage transformer) |
Operating threshold | 24…230 V AC/DC |
---|---|
Software Name | EcoStruxure Power Device: virtual injection test ESetup Easergy Pro |
Display type | 480 x 272 pixel color LCD |
Number of keys | 7 customizable |
Voltage indication | 10 x programmable 3-color LEDs 4 x programmable red LEDs |
Standards | IEC |
height | 176 mm |
Width | 152 mm |
Depth | 219 mm |
Weight | 3.5 kg maximum |
Reviews