Specifications

Main
Product range PowerLogic P5
Type of product or equipment Protection and relay control
Using the relay Maximum directional phase current
Product reference P5F30-BACD-GAAAA-AEAC
Circuit breaker type 30TE
Mounting the device Recessed
Mounting bracket Rack
Installation mode Detachable
Food 100…230 V AC
48…250 V DC
Measuring inputs : TC 1/5 A PHASE CURRENT 3
: TC 1/5 A residual current 1
: TC 1 A current 1
: voltage 4
: digital 15
Number of digital inputs (DI) 15
number of analogue inputs 0
Number of digital outputs (DO) 1 watchdog
12 logic
Number of analog outputs 0
Communication ports Front USB port 2
Cybersecurity Password protection
Communication port hardening
Firmware signature
Client IP address filter
Secure communication with associated tools
Protective functions Phase overcurrent 50/51
Directional phase overcurrent 67
Earth overcurrent 50N/51N
Directional earth overcurrent 67N
Transient intermittent 67NI
Neutral admission 21YN
Broken conductor 46 I2/I1
Selective overcurrent logic
Fault triggering (SOTF)
Circuit breaker failure 50BF
Directional active underpower 37P
Phase undercurrent 37
Long start, rotor lock 48/51LR
Motor restart inhibition 66
Negative sequence overcurrent 46
Overvoltage 59
Undervoltage 27 Positive sequence undervoltage 27P Residual overvoltage 59N
Underfrequency 81/81N Overfrequency 81/81N Restricted earth fault 64REF Lockout 86 CT supervision 60 VT supervision 60 H2 detection 68H2 H5 detection 68H5 Wattmetric earth fault 32N Programmable thresholds 99 Programmable curve Programmable logic 46 I2/I1 Current unbalance 46 I2/I1
 
Communication protocol No
Measuring functions Three-phase current
Zero sequence
current Positive component
current Negative component
current Ratio current between reverse and direct
Zero sequence voltage
Positive component voltage
Negative component
voltage Three- phase voltage
Residual voltage
Frequency
Synoptic phase voltage
Synoptic phase
current Current 2nd, 15th harmonics with TDH
Control functions Circuit breaker control and monitoring
Programmable interlock
Local/remote control
2 function keys
Programmable logic
Controllable devices 6 objects ordered + 2 objects monitored
Number of setting groups 4
Monitoring functions Trip circuit supervision 74
Circuit breaker supervision
Relay self-supervision
Registers and records Event recording
Recording of oscilloscope disturbances
Triggering context
Relay maintenance
Type of diagnostic cut-off organ TC/TP supervision ANSI code: 60
TC supervision
Tripping circuit supervision ANSI code: TCS
Connection mode Removable pin (logic input/output)
Removable eye lugs (current transformer)
Removable pin (voltage transformer)
Eye lugs (voltage transformer)
Complementary
Operating threshold 24…230 V AC/DC
Software Name EcoStruxure Power Device: virtual injection test
ESetup Easergy Pro
Display type 480 x 272 pixel color LCD
Number of keys 7 customizable
Voltage indication 10 x programmable 3-color LEDs
4 x programmable red LEDs
Standards IEC
height 176 mm
Width 152 mm
Depth 219 mm
Weight 3.5 kg maximum